Common Fault Handling Method of Flow Meter 2

5. Electromagnetic Flow meter


Electromagnetic Flow meter





Phenomenon
Cause
Measure

No flow signal output

1. Instrument power supply is not normal.
2. The cable is not connected properly.
3. Liquid flow conditions do not meet the requirements.
4. The sensor parts are damaged or the inner wall is attached.
5. The converter components are damaged.

1. Check whether the output of the power circuit board is normal.
2. Connect the cables correctly.
3. Check the flow direction of the liquid and whether the liquid in the tube is filled.
4. Regularly clean the covered liquid scar layer.
5. Replace the damaged components.

Output value
 fluctuation
1. Electromagnetic interference generated by external stray current.
2. The pipe is not filled with liquid or contains bubbles in the liquid.
3. The power supply board
is loose.
1. Check the instrument operating environment whether there is a large electrical or welding machine at work.
2. Make sure the liquid is full of tubes or bubbles are flattened.
3. Disassemble the flow meter and re-secure the circuit board.

The flow measurement value does not match the actual value
1. Transmitter circuit board
is broken down.
2. Liquid flow rate is too
low, containing tiny bubbles.
3. The signal cable is not connected properly.
4. The parameter setting of the converter is not accurate.
1. Check whether the transmitter circuit board is in good condition or not.
2. Ensure that the flow rate of the liquid under test is above the minimum flow limitation.
3. Check whether the signal cable connection and cable insulation are in good condition or not.
4. Re-set the converter settings value and verify the zero and full values of the converter.

Output signal
over range
1. Signal cable wiring is wrong.
2. The parameters of the
converter are set incorrectly.
3. The converter and sensor models are not matched.

1. Check the signal loop connection.
2. Check the parameters of the converter settings and zero, full compliance with the requirements.
3. Replace the converter and sensor models.

6. Vortex flow meter



Phenomenon
Cause
Measure

There is no output of
the flow meter
in the
pipe

No display No output in the
flow
meter

1. The power supply has failed.
2. The power supply is not connected.
3. The cable is disconnected or the border is faulty.

1. Re-supply or replace the power supply.
2. Turn on the power.
3. Reconnect the cable and check the
cable.

The instrument  
Shows
no output

1. The flow is too low to enter the measuring range.
2. There is a fault on the board.
3. The probe is damaged.
4. The pipe is blocked or the sensor is stuck.

1. Increase the flow or re-select the flow meter.
2. Replace the electronic board.
3. Replace the probe.
4. Re-install the flow meter.




Phenomenon

Cause

Measure

After power supplying, there is no
power flow but output
The output signal is
stable
1. The output frequency is 50 Hz frequency interference.
2. The magnifying plate is damaged and self-excited.
1. Use a shielded cable to re-connect
 the wiring.
2. Replace the amplifier.

The output signal has
changed

1. There is a strong electrical device or high frequency interference near the flow meter.
2. Pipeline has a strong shock.
3. Amplifier magnification or trigger sensitivity is too high.
4. Pipeline valve is not
completely closed, there is leakage.

1. Re-select the installation site.
2. Reinforce the piping of the flow meter mounting section.
3. Decrease the magnification (GB) or
sensitivity (SB) counterclockwise.
4. Check the valve.


Phenomenon

Cause

Measure
The
flow
output is
unstable

The reason of choose to
install extremely piping

1.There is a strong electrical interference signal, the instrument is not grounded, traffic and interference signal superposition.
2. Straight pipe is not enough or pipe diameter and meter diameter is inconsistent.
3.the impact of pipeline vibration.
4. flow meter installation is different.
5. the fluid is not full tube.
6. the flow below the lower limit or exceed the upper limit.
7. the existence of cavitation in the fluid phenomenon.

1. Re-connect the shield.
2. Replace the installation location again.
3. Reinforce the pipe to reduce vibration.
4. Re-install the meter.
5. Check the fluid flow and its instrument installation location.
6. Increase the flow rate or adjust the amplification plate filter parameters.
7. Install the valve of the instrument downstream, increase the back pressure.

Instrumentation reasons

1.The instrument menu is set incorrectly.
2.The motherboard is damaged.

1. Set the menu again as required.
2. Replace the motherboard.

7. Coriolis Mass Flowmeter



Phenomenon
Cause
Measure

Instantaneous flow is the maximum value

1. The cable is disconnected or the sensor is damaged.
2. The fuse inside the transmitter burns out.
3. The sensor measuring tube is blocked

1. Replace the cable or replace the sensor.
2. Replace the fuse.
3. After dredging, tap the sensor housing, and then measure the AC and DC voltage, still unsuccessful, that is due to the large installation of stress, then try to re-install.

When the flow rate increases, the
Flow meter indicates a negative
increase

The direction of the sensor flow is opposite to that of the housing, and the signal line is reversed.

Change the direction ofinstallation, and also change the signal line wiring.

When the fluid flows, the flows hows positive and
 negative beating, the range is large and sometimes
The negative maximum

1. Power supply AC and DC shielded cable ground is greater than 4Ω.
2. Pipeline vibration.
3. Fluid has two components, that is gas and liquid.
4. There is a strong magnetic field or radio frequency interference around the transmitter.

1. Re-ground.
2.Change the connection pipe with the flow meter to metal hose
connection.
3. Punch in the top of the flow meter pipe, and install the valve, used to discharge gas components.
4. Change the surroundings of the transmitter.

8. Ultrasonic flow sensor 




Ultrasonic flow meter

Phenomenon
Cause
Measure
Flow rate shows
dramatic changes
in data
The sensor is installed in a place where the pipe is vibrating or
installed downstream of the control valve, pump, orifice.
Install the sensor in a place away from vibration or move upstream of the changing flow regime.

The sensor is no problem, but the
flow rate is low
or no flow rate
1. Pipeline paint, rust is not clean.
2. The pipe surface is uneven or installed at the weld seam.
3. The sensor and the pipe coupling is not good, the coupling surface with cracks or bubbles.
4. The sensor is mounted on the casing, which will weaken the ultrasonic signal.
1. Clean the pipe and install the sensor.
2. Install the sensor with the pipe polished or away from the weld.
3. Re-install the coupling agent.
4. Move the sensor to the section with no casing.
The reading value is incorrect
1. The sensor is mounted on the top and bottom of the horizontal pipe, where the sediment interferes with the ultrasonic signal.
2.The sensor is mounted on a pipe with a downward flow of water and pipe is not filled with fluid.
1. Install the sensor on both sides of the pipe.
2. Install the sensor on a fluid-filled pipe section.
The flow meter is working properly and the flow
meter is no longer measuring the
flow

1. The measured medium changes.
2. The measured medium isgasifieddue to the high temperature.
3. The temperature of the measured medium exceeds the limit temperature of the sensor.
4. The coupling agent below the
sensor is aged or consumed.


1. Change the measurement method.
2. cool down.
3. Cooling.
4. Re-coat the coupling agent.
5. Keep away from sources of interference.
6. Reenter the value.

评论

此博客中的热门博文

FLOW TRANSMITTER WITH FLOW ELEMENT AND DIGITAL INDICATOR

The Working Principle of the Temperature Sensor Working for High

SHDP/GP Differential Pressure/Pressure Transmitter with Remote Diaphragm seals