The Flow Transmitter shall be preferably electromagnetic type and shall be supplied with Flow element and facility for fitment of Flow Indicator at local and remote location. These Flow Transmitters shall meet the following requirements in general:



Temperature range : 0-70°C

Type of sensing element : Electromagnetic flow sensor with microprocessor based signal converter

Type : Insertion with solid state transmitter

Enclosure type : Nema 4X

Protection : IP67

Input : 24VDC/220VAC 50 Hz

Output : 4-20 mA, 2 wire, HART

Flow rate of Water : 0-500 m3/hr

Pressure of water : 0-16 bar(working)–Max press 25 bar

Casing material : Stainless Steel

Accuracy : ± 0.5% of full scale

Material of Seals : Teflon

Other internal Parts : SS 304 / 316

Electrodes : SS 316

Socket connection size : ½” NTP with half coupling to connection

Connection Size/Type : 200 NB, Flanged as per ASA / ANSI



Connecting details of Flow Element with water pipes are to be provided. All the piping, flanges, unions, half couplings, valves and electrical components etc. required for installation of Flow Element and Transmitter shall be there.



Details of Electromagnetic Flow Sensor:


Flow Tube : SS304

Coil Housing : Fully welded, SS316 for meter

Electrodes : SS316 / SS316L & self cleaning type

Process connection : Flanged to ANSI 300#

Flanges : CS




Details of Electromagnetic Signal Converter:


Type : Microprocessor based

Bright graphic display : Large backlight with 2 line graphic

LC display parameters : Actual flow rate and totalizer

Housing : Die