FLOW TRANSMITTER WITH FLOW ELEMENT AND DIGITAL INDICATOR
The Flow Transmitter shall be preferably electromagnetic type and shall be supplied with Flow element and facility for fitment of Flow Indicator at local and remote location. These Flow Transmitters shall meet the following requirements in general: Temperature range : 0-70°C Type of sensing element : Electromagnetic flow sensor with microprocessor based signal converter Type : Insertion with solid state transmitter Enclosure type : Nema 4X Protection : IP67 Input : 24VDC/220VAC 50 Hz Output : 4-20 mA, 2 wire, HART Flow rate of Water : 0-500 m3/hr Pressure of water : 0-16 bar(working)–Max press 25 bar Casing material : Stainless Steel Accuracy : ± 0.5% of full scale Material of Seals : Teflon Other internal Parts : SS 304 / 316 Electrodes : SS 316 Socket connection size : ½” NTP with half coupling to connection Connection Size/Type : 200 NB, Flanged as per ASA / ANSI Connecting details of Flow Element with water pipes are to be provided. All the piping, flanges, unions, half coupling